B0046991 / Rev. 1.6
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
111
System parameter 7: Switching the password function on / off.
Fig.. 60: Switching the password on / off
Attention If no password is activated, then all parameters can be accessed
at any time. We recommend this only during starting-up the
system. For daily operation the password function should be
activated.
System parameter 8: Setting the output logic (0-sheet, 1-sheet, 2-sheet outputs).
Fig.. 61: Setting the output logic
Possible choices:
• 0 V: As shown in the timing diagrams and the wiring diagrams
• +24 V: The outputs 0-sheet, 1-sheet and 2-sheet are inverted, i.e. the respective signals in
the timing diagrams and wiring diagrams must be seen inverted.
Note The output “Enable“ is not affected thereby.
System parameter 9: Deactivating / activating the external calibration via fieldbus.
Fig.. 62: Deactivating / activating the external calibration
Here the external calibration, which is possible via PLC with the signals “teach-in“ and “zero
adjust“, can be deactivated / activated.
System parameter 10: Indication of system version.
Fig.. 63: Indication of system version, here 4P with 3 sensors, Version C, Opto coupler
This factory setting must not be changed!
system param. 7
password: yes
system param. 8
level 0-1-2:+24V
system param. 9
ext. adjust: no
System Param. 10
Version: 4P3 CO